Winter Maintenance Guide: Frozen pipes

A Winter Maintenance Guide to Preventing Frozen Pipes 

As the weather gets more frigid with each passing day in many parts of the world, it's important to be prepared for freezing temperatures. Frozen pipes are notoriously known to cause a significant amount of damage every year, and can result in thousands of dollars in damages if not handled correctly. When water freezes and expands, pressure builds, and vulnerable pipes are likely to burst. The smallest crack in a pipe can spew hundreds of gallons of water, resulting in flooding, mold, and structural damage. Unlike winter storms, bursting pipes are largely preventable with the right preparation. Here are a few tips on how to prevent frozen pipes, how to thaw frozen pipes before they burst, and how to avoid water damage before it’s too late:

Preventing Frozen Pipes

When temperatures drop below -6° C for at least six consecutive hours, pipes are at a risk of freezing. In order to mitigate the risk, it’s crucial to consider the following:

Insulate pipes: Pipes that are exposed, pipes that run through exterior walls, and pipes that are located in unheated crawl spaces, attics, and basements are all highly susceptible to freezing. To build thermal protection around pipes, it’s important to use materials like tubular foam, pipe wrap, and heat cable to raise water temperatures by -15.56° C.    

Seal leaks: Air leaks around electrical wiring and vents allow frigid temperatures to make their way around vulnerable pipes. Look for cracks around the building and tightly seal with caulk, weatherstripping, or additional insulation materials to keep cold air outside.

Keep consistent temperatures: Thermostats should be kept at a consistent temperature throughout the day and night. Dropping the temperature indoors at night may offer a lower heating bill, but adjusting below 12.78° C during extreme cold can cause a devastating strain on both pipes and furnaces.   

Thawing Frozen Pipes

If only a few drops of water trickle out of a faucet when it’s freezing outside, there’s a good chance the pipes are frozen. In this stage, it’s not too late to take action before they burst:  

Apply heat: Slowly apply heat using an electrical heating pad, a space heater, or hot towels. Be cautious of using appliances in areas of standing water to avoid electrocution. Start by warming the pipe as close to the faucet as possible, gradually moving towards the coldest portion of the pipe.   

Keep water running: While treating the pipes, keep faucets turned on to allow a consistent flow of water. As the frozen area begins to melt, running water will assist in preventing pressure buildup and blockages that can cause a burst. 

Check all faucets: If one pipe is frozen, it’s likely not an isolated situation. Check all faucets around the building for dripping water and repeat the heating process until all water pressure is restored.  

After Pipes Burst

When frozen pipes go undetected and untreated, ice blockages will likely cause pipes to burst. After the burst occurs, it’s critical to take immediate action. 

Contact a water restoration expert: When it comes to mold and bacteria, time is the enemy. Everything that comes into contact with water must be properly dried, cleaned and disinfected within 48 hours to avoid residual damage. Trained professionals know the quickest, safest, most efficient ways to salvage the building and its contents by measuring and recording temperature, moisture, and humidity.  

Shut off water: Locate the main water supply and shut it off to stop the heavy flow of water. Leave faucets on to relieve the pipe of remaining pressure and cold water. If the leak occurred near any electrical sockets or fuse boxes, it’s crucial to turn electricity off.  

Remove standing water: The longer water stays in the building, the higher potential for mold and mildew issues. Remove as much water and moisture from the area as possible, while waiting for the experts, using a durable dehumidifier and high-speed air mover. Carpeting, drywall, rugs, cloth, and other porous materials are the most vulnerable to damage.

But if disaster does strike, check out our blog on Disaster Restoration Solutions.

Winterization checklist: How to prepare your building for winter

Winterization checklist: How to prepare your building for winter

Avoid property damage with these quick tips

Winters in Canada and the northern U.S. are notoriously harsh. Each year, piled-up snow and ice damages roofs, and frozen pipes burst to wreak havoc on structures of all shapes and sizes. While winter storms are outside your control, preparing for them is not. 

Here are some quick tips to prepare your building for winter. 

Prevent Plumbing and Pipe Problems

One of the main threats that cold weather poses to buildings is frozen pipes. When pipes freeze, they burst, and the ensuing water damage can lead to mold growth, structural damage, and significant repair costs. Here’s what you can do to prepare:

  1. Keep inside temperature above 55F/12C to prevent freezing
  2. Check pipes for any air leaks
  3. If pipes are in non-insulated or non-heated areas, consider wrapping pipes in insulation to prevent freezing

Additionally, it’s best to expect the unexpected and prepare for the worst. In this case, that means having equipment on hand to handle flooding. When a pipe bursts and water spills into your building, the clock immediately begins ticking. Mold can form in just 24-72 hours. If you don’t have equipment on hand, you’ll be asking how to get rid of mold rather than how to prevent it. 

Here are some items you’ll want to have around in the case of a burst pipe:

  1. Air movers, such as the RAPTOR® RAM1000 Centrifugal Air Mover
  2. Dehumidifiers, such as the AQUATRAP® AT150RS LGR Dehumidifier

When flooding occurs, use air movers to dry the building and dehumidifiers to capture and remove the moisture in the air. 

Secure your Structure

Though snow may look light and fluffy when it’s falling, anyone who has shoveled snow knows that fluffy snowflakes accumulate into dense snow packs. While snow piling on your driveway may be little more than an annual inconvenience, snow piling on roofs can cause severe structural damage. 

The most dramatic example of structural damage from snow is roofs caving in. But this isn’t the only, or the most common, way that snow and ice on roofs can cause damage. The more common threat to structures from snow buildup is water damage. Snowmelt on roofs can leak into attics and cause mold growth. This can happen when shingles are missing or broken on the roofs, allowing water to seep through. 

Additionally, ice dams forming around gutters are a major concern. Like caved-in roofs, falling icicles causing serious injury or death to passersby are a dramatic example. More commonly, these icicles grow in size and weight, putting strain on gutters and causing them to break. When this happens, the falling gutters and ice can damage the rest of your structure and make exposed portions of the structure liable to water damage. 

Here’s what you can do to protect your roof from snow and ice:

  1. Clean the gutters, removing any leaves, debris, snow, or ice
  2. Inspect the roof, looking for missing or broken shingles
  3. Install heated cabling to warm your roof and prevent snow buildup

Have your HVAC’s Back

Your HVAC system has your back all year, keeping you cool in the summer and cozy in the winter. The least you can do is ensure it’s set up for success going into winter. As you put more strain on your HVAC system to heat your building throughout the cold winter months, here are a few things you can do to have its back:

  1. Change the filters
  2. Empty condensation traps
  3. Inspect the system for any blockages

Win with Winterization

At times, winter can feel like a primal battle between you and the elements. You never know what winter will throw at you, but by preparing for the worst, you set yourself up for success no matter what winter holds. This winter, be ready for anything with Abatement Technologies equipment at your disposal and win the battle against winter.

What to do When Flooding Occurs in a Hospital

What to do When Flooding Occurs in a Hospital

Hospitals, like all buildings, are subject to maintenance, repair, and restoration needs, sometimes at a moment's notice. Few building emergencies are worse than flooding. Whether it’s natural disasters flooding from heavy rain and hurricanes, or floods from equipment failure like burst pipes, floods are an emergency that can keep building managers up at night. This is perhaps more so in hospitals where increased regulations and patient safety concerns are cause for special precautions. 

Protecting Patients

When flooding occurs in a hospital and remediation is required, the number one priority is to protect patients throughout the process. After all, patients come to hospitals to be cured, not put in harm's way. In the case of hospital construction, maintenance, or restoration, one of the first steps is to construct containment walls around the affected area. Like isolating a patient, construction areas need isolation, too. With flooding, contractors need to contain the affected area to stop the spread of mold into adjacent spaces. In many cases, poly sheeting will be used to create a containment space. In high risk environments and larger disaster areas, drywall may be required. 

Once the containment is in place contractors create a negative pressure environment using HEPA-filtered negative air machines or portable air scrubbers. Creating a negative pressure environment helps ensure that unfiltered air inside the containment area does not leak out. The HEPA-filtered negative air machines and portable air scrubbers draw contaminated air in, filter the air, and then exhaust the filtered air out of the containment area through ductwork. Federal, state, provincial, local, and facility regulations will determine whether HEPA air can be discharged inside or whether it needs to be directed outside. 

Acting Fast

In cases of flooding, acting fast is imperative. Mold grows in 24-72 hours, and the longer a building stays wet, the longer mold has to grow. Once mold grows, it becomes much more difficult to get rid of and can be a health risk. Therefore, remediation teams must act fast. However, constructing traditional walls can take days. That’s where the SHIELD WALL® comes in. Unlike traditional walls, these lightweight polycarbonate walls are easy to transport and can be set up by a small team in a matter of hours, not days, allowing remediation teams to quickly get to work.

Reducing Waste

In an emergency, it’s a natural human instinct to get the job done as quickly as possible. One might choose to use whatever materials are readily available, which might not be the most financially conscious or sustainable route. Using single-use solutions only adds more to the financial burden. When hospitals construct temporary drywall walls to contain construction and remediation areas, the walls are discarded afterward. With skyrocketing lumber prices, this is an excess cost that adds up over time. With reusable containment walls, like the SHIELD WALL® System, companies can reuse the same containment walls for years in a row, saving money and promoting more sustainable business practices. 

Hospital Flood Abatement: A Case Study

Curious about what this looks like in real life? Request a case study below to learn how Northern Manitoba Regional Health protected patients, acted fast, and reduced waste by using the SHIELD WALL® System when a pipe burst overnight, dumping 70,000 gallons of water into a mechanical room and operating room. 

5 Years Later – How Abatement Technologies Aided Hurricane Maria

September is historically the time of year with the most optimal conditions for the formation of hurricanes in the mid-Atlantic region. Because of the high amounts of humidity and warm air in the Caribbean, its geographical location houses the perfect conditions for catastrophic hurricanes. In fact, this year marks the fifth anniversary of Hurricane Maria, the deadly Category 5 hurricane that devastated the northeastern Caribbean in September 2017.

As a result of Hurricane Maria, the island of Puerto Rico lost most of its essential services’ infrastructure, communities were leveled, many were displaced, and thousands of lives were lost. Five years after the disaster, the reconstruction and restoration efforts on the island are still ongoing. Following the immediate devastation in 2017, Abatement Technologies customer and restoration expert, Pat Dooley, was contracted to fly to San Juan, Puerto Rico, to do an assessment of the flood damage in the Mall of San Juan, a 1,580,000 square-foot shopping mall that first opened its doors in 2015. Upon initial assessment, Pat and his team discovered that nearly 18 inches of water had flooded the mall.

As a result of the hurricane, there were travel and equipment delays that prohibited Pat and his team from arriving in Puerto Rico until 14 days after the hurricane had already passed. Because mold incubates from a spore for 12 to 24 hours, and starts showing visual signs of growth in 48 to 72 hours, the team was challenged upon arrival with remediating severe mold growth. When remediating mold, it’s important to remove every spore to prevent regrowth. Because of this, workers had to cut and remove drywall and other materials, which lead to dust and other potentially harmful particles in the air.

In order to safely contain the mold, Pat and his team decided to bring in 100 of Abatement Technologies’ air filtration devices. These devices were situated throughout the mall to help remove any harmful particulates, bioaerosols and volatile organic compounds that were released into the air during the project. By leveraging this equipment, the team was able to help protect the short and long-term health of those involved and helped ensure that they were breathing the cleanest air possible. 

As a remediation and restoration expert, Pat is an IICRC Instructor and is the founder of what is known today as the Applied Structural Drying Course. Leveraging his education and experiences, like the project in Puerto Rico, Pat has carried out water restoration projects with a total value of nearly $14.7 million and has participated in numerous natural disaster restoration projects. With a passion for helping and protecting people, Abatement Technologies is proud to work with remediation and restoration experts, like Pat, to deliver the best solutions available in the market. 

Contact our team today to learn more about our air filtration devices and other restoration and remediation products! 

The Top 4 Considerations When Evaluating Portable Air Scrubbers

Airflow ratings can be very misleading: The cheapest units are often the most costly

When purchasing portable air scrubbers for use on restoration and/or mold remediation projects, there are many factors that should be considered in selecting the proper piece of equipment. Too many times airflow (or claimed airflow) and price are the only issues considered before a purchase.  All too often the contractor finds that the equipment does not meet their expectations or needs when it arrives. 

1. Ease of transport

This is one of the most important, yet most overlooked, aspects of portable air scrubbers. Scrubbers must constantly be moved from job to job and from location to location during a project. Some units are designed for one-person operation; others may require two people to move. Weight is very important, but so is weight distribution. Scrubbers that include a transport system for easy movement by one operator are safer and more cost-effective to operate. A stair climber is also a valuable feature when stairs are a factor. Size and weight should also be considered when thinking about transport and vehicle requirements.

2. Air scrubber filtration system

The filtration system is the heart of a portable air scrubber. Poorly designed filtration can add hundreds or even thousands of dollars in annual operating costs. Filters must provide a substantial dirt-holding capacity and long filter life without significant airflow loss. A well-designed filtration system requires three stages of filters to progressively filter all particle sizes. If odors and particulates are to be removed simultaneously, a fourth stage of gas/odor filtration may also be needed.

Easy “no tools” access is important when inspecting and replacing dirty filters. The filter module should not have to be removed to change or inspect filters. This is time consuming and can also cause debris to be spilled onto the HEPA and the surrounding area.

HEPA filters must be individually tested by the filter manufacturer and certified to a minimum efficiency of 99.97% at 0.3 microns. It is not enough to simply assemble a filter using HEPA media. A true HEPA filter must be constructed to the exact manufacturing practices necessary to ensure that the finished filter does not leak through the filter media or around the frame or seams. If debris can bypass the HEPA media, the filter will not pass DOP testing required in many abatement specifications. Insist that the HEPA filter itself be certified to HEPA standards, with a certification label affixed to the frame of the HEPA filter.

3. Blower type

Air scrubbers are required to trap large quantities of debris. Debris buildup on the filters hinders the airflow and causes what is technically known as static resistance. Specific blowers are much better suited than others for overcoming this resistance. There are many types of air moving blowers available, each with specific characteristics for certain applications. 

For example, forward-inclined “squirrel cage” blowers are designed to move large volumes of relatively clean air and low static resistance. These inexpensive blowers may be suitable for applications such as use in a furnace or even in an asbestos negative air machine; they are not, however, a very good selection for use in an air scrubber.

Backward-inclined or airfoil type blowers are a much better choice since they are engineered with the capacity to overcome the pressure drop of dirty filters. The use of this type of blower will not only increase filter life but will also produce higher airflow as the filters begin to accumulate debris. This generally means significantly better performance (airflow) over the life of the filters and much lower replacement filter expenses than a scrubber or negative air machine that is equipped with a forward inclined blower with a comparable peak airflow rating.

4. Materials and construction methods

Most negative air machines position the blower at the outlet of the cabinet, and pull air through the cabinet. This keeps the entire cabinet – including the section downstream from the HEPA filter - under lower (negative) pressure compared to the air in the surrounding area. With this design, the machine must be perfectly sealed to prevent contaminated air from being sucked into the cabinet and exhausted without ever passing through the HEPA.

This is a big concern when the unit is used as a negative air machine and exhausts air into another part of the facility, especially if that area is occupied. Any such leaks will negate the effectiveness of the HEPA filter and will more than likely cause contamination of the area and failure of any air testing required by the job specification. This should be an important liability concern of any mold abatement contractor.

Generally, the use of  gaskets and solid rivets produce the most leak free cabinets. Beware of any cabinet that uses fasteners such as hollow pop rivets, or threaded fasteners such as sheet metal screws or nuts and bolts. These devices do not afford the airtight seal necessary to keep small particles from infiltrating a negative pressure cabinet.

Fun fact: It has been found that sub-micron particles can actually travel along the threads of a screw or bolt!

Lastly, make certain that any hardware, instruments, or transport system components that penetrate into the cabinet are sealed in such a way as to prevent any leakage or bypass. For more information on evaluating portable air scrubbers contact us!

The Secrets of Negative Pressure Containment

The Secrets of Negative Pressure Containment

The average hospital lasts more than 40 years, and often as many as 100 years. If you've ever considered buying an old house, or seen others do it on TV, you know just how much renovation and maintenance they require. Now multiply the square footage by more than 10, and you can imagine how much renovation is consistently needed in hospitals not only to keep them going but to continually improve services and meet changing building requirements.

While renovation and maintenance projects may pose little more than an inconvenience to homeowners, they require special attention in healthcare facilities because of the danger that airborne particles, spores, and pathogens released into the air by construction pose to patients. In order to carry out essential construction and maintenance work without harming patients, construction zones must be sealed off from patients, and air must be filtered and diverted away from vulnerable patients. 

To do this, facilities must perform Negative Pressure Containment. 

What is Negative Pressure Containment?

By its very definition, a negative pressure room has more air exiting it then entering. There is less air inside the room compared to the other rooms, hence why it is negative. What this does is ensures that any airflow outside of the HEPA exhaust is flowing into the room to fill that vacuum. Because airflow can only flow in one direction through the cracks or designated makeup air locations, the contaminants cannot escape the room.  Always check regulations when exhausting inside a healthcare facility as regulations can vary.

How to create Negative Pressure Containment

There are four key steps to creating negative pressure containment:

1. Construct a physical barrier around the area. 

Product Tip: You can do this with Abatement Technologies' AIRE GUARDIAN® SHIELD

2. Seal off any HVAC Returns

Tip: This ensures that dirty air does not escape into the rest of the building. 

3. Filter air in the sealed room with a portable air scrubber (PAS)

Product Tip: Use a HEPA-AIRE® or PREDATOR® series Portable Air Scrubber (PAS) from Abatement Technologies.

4. Use a PAS (portable air scrubber) to exhaust the filtered air out the construction zone through duct work

Product Tip: Find compatible duct here

Get it right everytime

Before attempting to create negative pressure, use our air change calculator to determine your airflow needs. Once you’ve followed the four steps above, use a portable differential pressure monitor for the most accurate reading of your negative pressurization. 

Ready to learn more about Abatement Technologies? Contact us today!

Critical Environment Protection

Critical Environment Protection

HEPA based high-quality air filtration equipment

A Critical Environment is any area where something can be easily affected by external contamination. Our experience working with companies that have to do dirty jobs in critical environments started in the 80's with asbestos abatement. The job of removing asbestos required contractors to enlist preventative measures to control dangerous dust particles and that's where we found our niche and specialty. Making high-quality air filtration equipment that incorporated HEPA filtration to remove 99.97% of any airborne particulate that was 0.3 microns or larger.

This created a natural expansion into healthcare construction, as infrastructures age the need to renovate facilities without shutting them, because these types of renovations would be happening alongside occupied patient areas and patients, especially those that are immunocompromised and susceptible to infection from the slightest airborne contamination our specialized equipment was again brought into play, by allowing contractors to contain their construction site and use negative pressure and HEPA level filtration to help prevent the spread of those dangerous contaminants to patient occupied areas.

Recently we have seen the expansion of what would be considered critical environments. These include Pharmaceutical Manufacturing and Storage Facilities, Electronics Manufacturing Facilities, Food and Beverage Manufacturing, Data Centers and Server Rooms as well as the expanded concern about construction around employees in any operational work environment.

Our high-end selection of HEPA based air filtration equipment, portable containment solutions, temporary barriers systems, and pressure monitoring equipment combined with our knowledgeable sales consultants make Abatement Technologies the perfect partner for a project in any critical environment.

Principles and importance of negative pressure containment

Dust control equipment and containment barriers create a cleaner, healthier environment for employees, sensitive equipment and manufacturing processes.

Learn how our dust control and air purification products can help maintain a productive indoor environment during construction in government facilities, office buildings, schools & universities, retail operations, storage facilities and manufacturing operations.

Product selection and application assistance

High-efficiency, HEPA-filter dust control equipment and containment barriers from Abatement Technologies® can help isolate and remove particles released into the air during construction, renovation and day-to-day maintenance activities. Our state-of-the-art, cost-effective solutions are used every day to help protect workers, building occupants and production lines from exposure to hazardous pollutants and odors that can negatively impact employee health, comfort and damage sensitive equipment. Abatement Technologies® particle control products can also save time and money by reducing clean-up labor during and after the job.

Learn how our dust control and air purification products can help maintain a productive indoor environment during construction in government facilities, office buildings, schools & universities, retail operations, storage facilities and manufacturing operations.

Contact us for more information! 

Disaster Restoration Solutions

Disaster Restoration Solutions

Abatement Technologies® offers a full line of equipment, products and chemicals to help fire and water restoration contractors and mold abatement contractors increase productivity and dry structures faster. Our industry specialists are available to answer product questions or discuss drying solutions on your restoration job. 

US and Canadian workplace safety regulations require certified electrical equipment.

OSHA safety regulations in the U.S. and CAN/CSA regulations in Canada require all electrical device models used in the workplace to conform to applicable safety standards. This means that the device must be submitted by the manufacturer to an OSHA Certified Nationally Recognized Testing Laboratory (NRTL) such as UL, TUV, ETL or CSA for the specified certification testing.

HEPA filtration devices  such as portable air scrubbers and axial and centrifugal air movers must conform to the UL507 “Fans and Blowers” standard. Devices with plastic cabinets (enclosures) that contain energized electrical components must be NRTL certified to conform to UL flammability standards (typically UL94HB) as well.

The unfortunate truth 

 A significant number of the HEPA filtration devices, air movers and other devices sold and in wide use today are not NRTL certified. This problem appears to be particularly prevalent with devices imported from Asia, but applies to some products made right here in North America as well. It’s possible that some of these products might comply if submitted to and tested by an NRTL, but it appears likely that at least some would fail.

It costs money to design and build products that can conform to these safety standards. Uncertified devices may be available at a lower price, but isn’t that like playing Russian roulette? Without the proper safety certifications how can you possibly know whether or not the product is safe? With all that could be at stake is the chance to perhaps save a few bucks up front a risk that you can really afford to take?

Product safety is one of our paramount concerns

That’s why each and every Abatement Technologies portable air scrubber and air mover  model sold in the U.S. and Canada has been tested by a Nationally Recognized Testing Laboratory (NRTL) and certified to conform to UL507. All models made with polymer cabinets have also been NRTL tested and certified to conform to stringent UL94HB flammability standards.

Best Practices

All NRTL certified products must have an NRTL certification label attached to them to show that they are compliant. It might be a good time to take a few minutes to inspect your equipment and check for the labels. If they are not there it might be time to call your supplier and find out why. Or, it might be time to look for another brand that is certified. 

If you need assistance finding compliant equipment, our sales representatives are happy to help!  Contact Us

 
Translate
 

7 FAQ’s About Asbestos Abatement Equipment

7 FAQ's About Asbestos Abatement Equipment

Frequently asked questions about HEPA-AIRE® Negative Air Machines for asbestos abatement.

Does the machine actually produce the airflow you think you’re getting?

One of the most confusing, inaccurate and potentially misleading methods of testing this is ‘free air’, which is nothing more than the test bench rating of the blower. The airflow produced by the device will be up to 60% lower when the blower is enclosed in a cabinet and must pull air through the resistance of the filters.

The airflow comparison chart shows that the true airflow of negative air machines can vary substantially from brand-to-brand because different suppliers use different rating methods and components. Click here to view the chart.

Does the HEPA filter truly provide 99.97% HEPA filtration?

A filter made with HEPA media may or may not provide true HEPA efficiency. Serious leakage can go undetected if filters are not individually tested and certified at the end of the manufacturing process in accordance with IEST-RP-CC001.3 guidelines for Type A HEPA filters. Even the tiniest pinhole leaks in the media or breach of the seal between the media pack and the filter frame can cause the filter to fail efficiency requirements. If this happens, contaminated air can pass through the filter and be exhausted into ‘clean’ areas of the facility.

HEPA testing requires very specific procedures using a thermally generated mono-dispersed aerosol and a laser particle counter. Test results, including test airflow, percent penetration, date of manufacture and other detailed information must be included on a label affixed to the filter. Testing should be conducted at the rated airflow of the machine. A filter designed for and tested at 1,000 cfm or 1,100 cfm may provide significantly lower efficiency at 2,000 cfm. If the filter label simply states “99.97% HEPA Filter” or “2,000 CFM HEPA Filter”, but does not include all of the detailed testing information, it’s probable that the filter has not been individually tested.

Is the machine designed to prevent bypass leakage around the HEPA filter?

Even the best HEPA filter can’t prevent contamination problems if the machine is not designed to prevent contaminated air from bypassing the filter. Look for important contaminated air bypass prevention features such as:

• Flat, rigid HEPA sealing frames with no welds or other surface irregularities that can disrupt the seal

• Seamless poured closed-cell neoprene gaskets or silicone gel seals as opposed to gaskets with seams or made from open cell foam

• Solid rivet fasteners versus weaker and potentially leaky hollow pop-rivets or metal screws.

• Sealed control panels

Is the machine safe?

Why take the chance on an untested and potentially unsafe machine? OSHA (U.S.) and CSA (Canada) require electrical safety testing and certification by an approved Nationally Recognized Testing Laboratory (NRTL), such as UL, CSA or ETL. This overall testing is required even if the individual electrical components are all NRTL listed.

Contractors may be surprised to learn that the HEPA-AIRE® Negative Air Machines manufactured by Abatement Technologies® are currently one of the few brands that meets these requirements. All Abatement Technologies negative air machine models are certified by a Nationally Recognized Testing Laboratory (NRTL)., and carry their ETL/ETLC mark for safe operation on 115V/15A electrical supplies.

What makes HEPA filters so efficient?

The ultra-fine, glass-fiber medium captures microscopic particles that can easily pass through other filters by a combination of diffusion, interception and inertial impaction. To qualify as a Type A HEPA filter, the filter must capture at least 99.97% of particles 0.3 microns in size–about 300 times smaller than the diameter of a human hair, and 25 to 50 times smaller than we can see.  To a HEPA filter, catching a one-micron particle is like stopping a cotton ball with a door screen.

Why is the testing done with a 0.3-micron particle size test aerosol?

Filter efficiency studies have shown that 0.3-microns is the "Most Penetrating Particle Size (MPPS)" for HEPA filter media. Efficiency is typically greater than 99.97% against larger or smaller particle sizes. Particles larger than 0.3 microns are typically more easily trapped, or intercepted, by the media. Smaller particles often lack sufficient mass to penetrate the media.

Does HEPA efficiency decrease as the filter gets dirty?

No. The dirtier a HEPA filter gets, the more efficient it typically becomes.

Have another question? Contact us

Things To Consider Before Comparing Airflow Ratings

 

Things to Consider Before Comparing Airflow Ratings

Why airflow ratings can be very misleading and the cheapest units are often the most costly.

No industry-standard airflow rating method

There is no standardized method that manufacturers use to rate the airflow of their air filtration devices. Different methods can produce widely varying and often misleading results, and make direct comparisons between brands difficult if not impossible.

Compare ‘Apples & Oranges’

The most overstated and inaccurate method used bases device airflow ratings on the AMCA “free air” blower rating, which is a test bench measurement of the airflow the blower can produce at various motor horsepower levels with no static resistance. Since actual peak airflow with the cabinet and filters in place is typically 50% to 80% lower, free air is essentially meaningless when it comes to rating the device itself.

Inlet or outlet readings with an air-straightening duct attached to reduce turbulence are far more accurate. This testing is generally done using a computing vane anemometer or pitot tube traverse to determine the average velocity (in feet per minute) and airflow (in cubic feet per minute) flowing through the air straightening duct. Attempting to measure airflow at non-laminar inlet and outlet openings is not recommended.

Peak airflow is only part of the story

Even when accurate, peak airflows can be misleading because they provide only a small part of the performance picture. It's often a mistake to automatically conclude that the performances of two devices are equal just because their peak airflows are similar. The airflow of all filtration devices drop off as resistance to airflow increases due to filter loading, external collars or flex duct. The magnitude and frequency of these losses; and therefore how frequently filters must be replaced to restore acceptable airflow levels can vary greatly.

Peak static capacity of the blower and filter dirt holding capacity are the main factors that determine 'real life' airflow and filter life. As a rule, a backward curved blower can move more air than a cheaper but less efficient squirrel-cage blower, due largely to its ability to operate at much higher 'tip speeds' and therefore overcome higher levels of resistance. This higher capacity, in turn, extends the useful life of the filters and can make a higher price but more efficient system far less costly to operate.

Build in a sufficient margin of safety

To compensate for airflow losses, users should build in a safety margin when estimating how many units are required to provide a given number of ACH (air changes per hour). If the objective is 6 ACH, designing for 8 or 9 ACH at peak airflow should be more than adequate to ensure sufficient airflow throughout the filter loading cycle provided that the peak airflow rating is reasonably accurate.

See which, and how many units you would need for the appropriate amount of air changes per hour based on your room size with our Air Change Calculator

Contact us for more information!

 

Translate
 
Translate